Technical specifications

Frequency
50
K Factor
13
Input voltage
400
Output voltage
400
Primary winding connection
Delta
Secondary winding connection
Star + N
Vector unit
Dyn11
Core material
M270 magnetic steel
Winding material
Aluminium
Electrostatic shield
Between primary & secondary, connected to ground
Max ambient temperature
40
Insulation class
H
Insulation level
3
Thermal class
H
Temperature rise
125
Max altitude
1000
Environmental - climate - fire class
E1 - C1 - F0
Installation
Indoor
Protection degree
  • IP00
Reference Standards
EN 60076 / IEC 61558 (when applicable)

DYN11 K13 AL IP00

part number
power
in-rush current
no-load losses
load losses
vcc %
Data Sheet
DYN11 K13 AL IP00 30
30
24
350
850
4
DYN11 K13 AL IP00 40
40
15
410
1000
4
DYN11 K13 AL IP00 50
50
15
450
1080
4
DYN11 K13 AL IP00 63
63
15
630
1150
4
DYN11 K13 AL IP00 70
70
15
680
1210
4
DYN11 K13 AL IP00 80
80
15
740
1320
4
DYN11 K13 AL IP00 90
90
13
780
1380
4
DYN11 K13 AL IP00 100
100
13
870
1520
4
DYN11 K13 AL IP00 110
110
13
920
1640
4
DYN11 K13 AL IP00 125
125
13
960
1880
4
DYN11 K13 AL IP00 140
140
12
1100
1980
4
DYN11 K13 AL IP00 160
160
11
1200
2120
4
DYN11 K13 AL IP00 180
180
11
1290
2280
4
DYN11 K13 AL IP00 200
200
10
1430
2420
4
DYN11 K13 AL IP00 225
225
10
1470
2620
4
DYN11 K13 AL IP00 250
250
10
1620
2850
4
DYN11 K13 AL IP00 280
280
10
1730
3180
4
DYN11 K13 AL IP00 315
315
9
1890
3600
4
DYN11 K13 AL IP00 350
350
9
2100
4100
4
DYN11 K13 AL IP00 400
400
9
2250
4530
4
DYN11 K13 AL IP00 500
500
8
2780
5250
4
DYN11 K13 AL IP00 630
630
7
3000
6180
4
DYN11 K13 AL IP00 800
800
6
4050
7180
4.5
DYN11 K13 AL IP00 1000
1000
6
4950
8450
4.5
DYN11 K13 AL IP00 1250
1250
5
6200
10400
5
DYN11 K13 AL IP00 1600
1600
5
7600
12250
5