Technical specifications

Frequency
50
K Factor
20
Input voltage
400
Output voltage
400
Primary winding connection
Delta
Secondary winding connection
Zig-zag
Vector unit
Dzn0
Core material
M270 magnetic steel
Winding material
Copper
Electrostatic shield
Between primary & secondary, connected to ground
Max ambient temperature
40
Insulation class
H
Insulation level
3
Thermal class
H
Temperature rise
125
Max altitude
1000
Environmental - climate - fire class
E1 - C1 - F0
Installation
Indoor
Protection degree
  • IP21
Reference Standards
EN 60076 / IEC 61558 (when applicable)

DZN0 K20 CU IP21

part number
power
in-rush current
no-load losses
load losses
vcc %
Data Sheet
DZN0 K20 CU IP21 7
7
46
160
230
3.5
DZN0 K20 CU IP21 9
9
46
180
290
3.5
DZN0 K20 CU IP21 10
10
46
190
360
3.5
DZN0 K20 CU IP21 14
14
46
225
390
3.5
DZN0 K20 CU IP21 18
18
46
260
470
3.5
DZN0 K20 CU IP21 22
22
37
290
550
3.5
DZN0 K20 CU IP21 28
28
29
330
570
4
DZN0 K20 CU IP21 36
36
27
360
650
4
DZN0 K20 CU IP21 45
45
22
410
760
4
DZN0 K20 CU IP21 58
58
21
470
890
4
DZN0 K20 CU IP21 63
63
20
510
970
4
DZN0 K20 CU IP21 70
70
18
540
1060
4
DZN0 K20 CU IP21 80
80
17
580
1130
4
DZN0 K20 CU IP21 90
90
17
630
1260
4
DZN0 K20 CU IP21 100
100
15
680
1370
4
DZN0 K20 CU IP21 110
110
14
740
1530
4
DZN0 K20 CU IP21 125
125
14
810
1680
4
DZN0 K20 CU IP21 140
140
13
870
1840
4
DZN0 K20 CU IP21 160
160
13
940
2030
4
DZN0 K20 CU IP21 180
180
11
1020
2220
4
DZN0 K20 CU IP21 200
200
11
1100
2450
4
DZN0 K20 CU IP21 225
225
10
1200
2710
4
DZN0 K20 CU IP21 250
250
10
1290
2960
4
DZN0 K20 CU IP21 280
280
8
1410
3320
4
DZN0 K20 CU IP21 315
315
8
1520
3680
4
DZN0 K20 CU IP21 350
350
8
1620
4020
4
DZN0 K20 CU IP21 450
450
7
1840
4880
4