Technical specifications

Frequency
50
K Factor
13
Input voltage
400
Output voltage
400
Primary winding connection
Delta
Secondary winding connection
Star + N
Vector unit
Dyn11
Core material
M270 magnetic steel
Winding material
Copper
Electrostatic shield
Between primary & secondary, connected to ground
Max ambient temperature
40
Insulation class
H
Insulation level
3
Thermal class
H
Temperature rise
125
Max altitude
1000
Environmental - climate - fire class
E1 - C1 - F0
Installation
Indoor
Protection degree
  • IP00
Reference Standards
EN 60076 / IEC 61558 (when applicable)

DYN11 K13 CU IP00

part number
power
in-rush current
no-load losses
load losses
vcc %
Data Sheet
DYN11 K13 CU IP00 8
8
40
150
280
3.5
DYN11 K13 CU IP00 10
10
40
170
340
3.5
DYN11 K13 CU IP00 12
12
40
180
420
3.5
DYN11 K13 CU IP00 15
15
37.5
210
460
3.5
DYN11 K13 CU IP00 20
20
37.5
240
550
3.5
DYN11 K13 CU IP00 25
25
31.25
270
640
3.5
DYN11 K13 CU IP00 30
30
25
340
680
4
DYN11 K13 CU IP00 40
40
23
400
760
4
DYN11 K13 CU IP00 50
50
21
460
860
4
DYN11 K13 CU IP00 63
63
19
530
1000
4
DYN11 K13 CU IP00 70
70
18
570
1080
4
DYN11 K13 CU IP00 80
80
17
610
1150
4
DYN11 K13 CU IP00 90
90
17
650
1240
4
DYN11 K13 CU IP00 100
100
16
700
1350
4
DYN11 K13 CU IP00 110
110
15
750
1470
4
DYN11 K13 CU IP00 125
125
14
820
1620
4
DYN11 K13 CU IP00 140
140
14
880
1770
4
DYN11 K13 CU IP00 160
160
13
940
1920
4
DYN11 K13 CU IP00 180
180
13
1010
2110
4
DYN11 K13 CU IP00 200
200
12
1080
2290
4
DYN11 K13 CU IP00 225
225
12
1160
2520
4
DYN11 K13 CU IP00 250
250
11
1250
2760
4
DYN11 K13 CU IP00 280
280
11
1340
3010
4
DYN11 K13 CU IP00 315
315
10
1460
3370
4
DYN11 K13 CU IP00 350
350
10
1570
3710
4
DYN11 K13 CU IP00 400
400
9
1670
4040
4
DYN11 K13 CU IP00 500
500
8
1930
4880
4
DYN11 K13 CU IP00 630
630
8
2250
5910
4
DYN11 K13 CU IP00 800
800
7
2580
7000
4.5