part number
|
power
|
in-rush current
|
no-load losses
|
load losses
|
vcc %
|
Data Sheet
|
---|---|---|---|---|---|---|
DYN11 K13 R IP00 8
|
8
|
40
|
150
|
280
|
3.5
|
|
DYN11 K13 R IP00 10
|
10
|
40
|
170
|
340
|
3.5
|
|
DYN11 K13 R IP00 12
|
12
|
40
|
180
|
420
|
3.5
|
|
DYN11 K13 R IP00 15
|
15
|
37.5
|
210
|
460
|
3.5
|
|
DYN11 K13 R IP00 20
|
20
|
37.5
|
240
|
550
|
3.5
|
|
DYN11 K13 R IP00 25
|
25
|
31.25
|
270
|
640
|
3.5
|
|
DYN11 K13 R IP00 30
|
30
|
25
|
340
|
680
|
4
|
|
DYN11 K13 R IP00 40
|
40
|
23
|
400
|
760
|
4
|
|
DYN11 K13 R IP00 50
|
50
|
21
|
460
|
860
|
4
|
|
DYN11 K13 R IP00 63
|
63
|
19
|
530
|
1000
|
4
|
|
DYN11 K13 R IP00 70
|
70
|
18
|
570
|
1080
|
4
|
|
DYN11 K13 R IP00 80
|
80
|
17
|
610
|
1150
|
4
|
|
DYN11 K13 R IP00 90
|
90
|
17
|
650
|
1240
|
4
|
|
DYN11 K13 R IP00 100
|
100
|
16
|
700
|
1350
|
4
|
|
DYN11 K13 R IP00 110
|
110
|
15
|
750
|
1470
|
4
|
|
DYN11 K13 R IP00 125
|
125
|
14
|
820
|
1620
|
4
|
|
DYN11 K13 R IP00 140
|
140
|
14
|
880
|
1770
|
4
|
|
DYN11 K13 R IP00 160
|
160
|
13
|
940
|
1920
|
4
|
|
DYN11 K13 R IP00 180
|
180
|
13
|
1010
|
2110
|
4
|
|
DYN11 K13 R IP00 200
|
200
|
12
|
1080
|
2290
|
4
|
|
DYN11 K13 R IP00 225
|
225
|
12
|
1160
|
2520
|
4
|
|
DYN11 K13 R IP00 250
|
250
|
11
|
1250
|
2760
|
4
|
|
DYN11 K13 R IP00 280
|
280
|
11
|
1340
|
3010
|
4
|
|
DYN11 K13 R IP00 315
|
315
|
10
|
1460
|
3370
|
4
|
|
DYN11 K13 R IP00 350
|
350
|
10
|
1570
|
3710
|
4
|
|
DYN11 K13 R IP00 400
|
400
|
9
|
1670
|
4040
|
4
|
|
DYN11 K13 R IP00 500
|
500
|
8
|
1930
|
4880
|
4
|
|
DYN11 K13 R IP00 630
|
630
|
8
|
2250
|
5910
|
4
|
|
DYN11 K13 R IP00 800
|
800
|
7
|
2580
|
7000
|
4.5
|