Technical specifications

Frequency
50
K Factor
13
Input voltage
400
Output voltage
400
Primary winding connection
Delta
Secondary winding connection
Zig-zag
Vector unit
Dzn0
Core material
M270 magnetic steel
Winding material
Copper
Electrostatic shield
Between primary & secondary, connected to ground
Max ambient temperature
40
Insulation class
H
Insulation level
3
Thermal class
H
Temperature rise
125
Max altitude
1000
Environmental - climate - fire class
E1 - C1 - F0
Installation
Indoor
Protection degree
  • IP00
Reference Standards
EN 60076 / IEC 61558 (when applicable)

DZN0 K13 R IP00

part number
power
in-rush current
no-load losses
load losses
vcc %
Data Sheet
DZN0 K13 R IP00 8
8
40
160
290
3.5
DZN0 K13 R IP00 10
10
40
180
360
3.5
DZN0 K13 R IP00 12
12
40
190
450
3.5
DZN0 K13 R IP00 15
15
40
225
490
3.5
DZN0 K13 R IP00 20
20
40
260
590
3.5
DZN0 K13 R IP00 25
25
32
290
680
3.5
DZN0 K13 R IP00 30
30
26
330
720
4
DZN0 K13 R IP00 40
40
24
360
820
4
DZN0 K13 R IP00 50
50
20
410
950
4
DZN0 K13 R IP00 63
63
19
470
1120
4
DZN0 K13 R IP00 70
70
18
510
1220
4
DZN0 K13 R IP00 80
80
16
540
1320
4
DZN0 K13 R IP00 90
90
15
580
1420
4
DZN0 K13 R IP00 100
100
15
630
1570
4
DZN0 K13 R IP00 110
110
14
680
1720
4
DZN0 K13 R IP00 125
125
13
740
1920
4
DZN0 K13 R IP00 140
140
13
810
2110
4
DZN0 K13 R IP00 160
160
11
870
2310
4
DZN0 K13 R IP00 180
180
11
940
2550
4
DZN0 K13 R IP00 200
200
10
1020
2790
4
DZN0 K13 R IP00 225
225
10
1100
3070
4
DZN0 K13 R IP00 250
250
9
1200
3400
4
DZN0 K13 R IP00 280
280
9
1290
3720
4
DZN0 K13 R IP00 315
315
8
1410
4170
4
DZN0 K13 R IP00 350
350
8
1520
4610
4
DZN0 K13 R IP00 400
400
8
1620
5040
4
DZN0 K13 R IP00 500
500
6
1840
6120
4