Technical specifications

Frequency
50
K Factor
13
Input voltage
400
Output voltage
400
Primary winding connection
Delta
Secondary winding connection
Zig-zag
Vector unit
Dzn0
Core material
M270 magnetic steel
Winding material
Copper
Electrostatic shield
Between primary & secondary, connected to ground
Max ambient temperature
40
Insulation class
H
Insulation level
3
Thermal class
H
Temperature rise
125
Max altitude
1000
Environmental - climate - fire class
E1 - C1 - F0
Installation
Indoor
Protection degree
  • IP21
Reference Standards
EN 60076 / IEC 61558 (when applicable)

DZN0 K13 CU IP21

part number
power
in-rush current
no-load losses
load losses
vcc %
Data Sheet
DZN0 K13 CU IP21 8
8
40
160
290
3.5
DZN0 K13 CU IP21 10
10
40
180
360
3.5
DZN0 K13 CU IP21 12
12
40
190
450
3.5
DZN0 K13 CU IP21 15
15
40
225
490
3.5
DZN0 K13 CU IP21 20
20
40
260
590
3.5
DZN0 K13 CU IP21 25
25
32
290
680
3.5
DZN0 K13 CU IP21 30
30
26
330
720
4
DZN0 K13 CU IP21 40
40
24
360
820
4
DZN0 K13 CU IP21 50
50
20
410
950
4
DZN0 K13 CU IP21 63
63
19
470
1120
4
DZN0 K13 CU IP21 70
70
18
510
1220
4
DZN0 K13 CU IP21 80
80
16
540
1320
4
DZN0 K13 CU IP21 90
90
15
580
1420
4
DZN0 K13 CU IP21 100
100
15
630
1570
4
DZN0 K13 CU IP21 110
110
14
680
1720
4
DZN0 K13 CU IP21 125
125
13
740
1920
4
DZN0 K13 CU IP21 140
140
13
810
2110
4
DZN0 K13 CU IP21 160
160
11
870
2310
4
DZN0 K13 CU IP21 180
180
11
940
2550
4
DZN0 K13 CU IP21 200
200
10
1020
2790
4
DZN0 K13 CU IP21 225
225
10
1100
3070
4
DZN0 K13 CU IP21 250
250
9
1200
3400
4
DZN0 K13 CU IP21 280
280
9
1290
3720
4
DZN0 K13 CU IP21 315
315
8
1410
4170
4
DZN0 K13 CU IP21 350
350
8
1520
4610
4
DZN0 K13 CU IP21 400
400
8
1620
5040
4
DZN0 K13 CU IP21 500
500
6
1840
6120
4