Technical specifications

Frequency
50Hz ±5% o 60Hz ±5%
Adjusting energy parameters
Independent phase control
Selectable target voltage
from 210V to 240V (L-N) / from 364V to 416V (L-L)
Output voltage accuracy
±0,5%
Admitted load variation
Up to 100%
Admitted load imbalance [%]
100
Cooling
Natural ventilation (from 35°C aided with fans)
Ambient temperature
-25/+45°C
Storage temperature
-25/+60°C
Max related humidity
<95% (non condensing)
Admitted overload
200% 2min.
Harmonic distorsion
None introduced
Colour
RAL 7035
Installation
Indoor
Instrumentation
EnerCloud Platform
Overvoltage protection
  • Class I input surge arrestors
  • Class II output surge arrestors
  • Optimal voltage return through supercapacitors in case of black-out
Additional protections
  • Electronic automatic by-pass system
  • Emergency manual by-pass system
  • Integral exclusion by-pass system

type
rated power
input voltage range [v]
max input current
related voltage
max output current
Data Sheet
100-10E
100
Vout ±10%
160
400
144
160-10E
160
Vout ±10%
257
400
231
250-10E
250
Vout ±10%
401
400
361
315-10E
315
Vout ±10%
505
400
455
400-10E
400
Vout ±10%
642
400
577
500-10E
500
Vout ±10%
802
400
722
630-10E
630
Vout ±10%
1010
400
909
800-10E
800
Vout ±10%
1283
400
1155
1000-10E
1000
Vout ±10%
1604
400
1443
1250-10E
1250
Vout ±10%
2005
400
1804
1600-10E
1600
Vout ±10%
2566
400
2309
2000-10E
2000
Vout ±10%
3208
400
2887
2500-10E
2500
Vout ±10%
4009
400
3609
3200-10E
3200
Vout ±10%
5132
400
4619