Technical specifications

Frequency
50Hz ±5% o 60Hz ±5%
Adjusting energy parameters
Independent phase control
Selectable target voltage
from 210V to 240V (L-N) / from 364V to 416V (L-L)
Output voltage accuracy
±0,5%
Admitted load variation
Up to 100%
Admitted load imbalance [%]
100
Cooling
Natural ventilation (from 35°C aided with fans)
Ambient temperature
-25/+45°C
Storage temperature
-25/+60°C
Max related humidity
<95% (non condensing)
Admitted overload
200% 2min.
Harmonic distorsion
None introduced
Colour
RAL 7035
Installation
Indoor
Instrumentation
EnerCloud Platform
Overvoltage protection
  • Class I input surge arrestors
  • Class II output surge arrestors
  • Optimal voltage return through supercapacitors in case of black-out
Additional protections
  • Electronic automatic by-pass system
  • Emergency manual by-pass system

type
rated power
input voltage range [v]
max input current
related voltage
max output current
Data Sheet
100-20
100
Vout ±20%
180
400
144
160-20
160
Vout ±20%
289
400
231
250-20
250
Vout ±20%
451
400
361
315-20
315
Vout ±20%
568
400
455
400-20
400
Vout ±20%
722
400
577
500-20
500
Vout ±20%
902
400
722
630-20
630
Vout ±20%
1137
400
909
800-20
800
Vout ±20%
1443
400
1155
1000-20
1000
Vout ±20%
1804
400
1443
1250-20
1250
Vout ±20%
2255
400
1804
1600-20
1600
Vout ±20%
2887
400
2309
2000-20
2000
Vout ±20%
3609
400
2887
2500-20
2500
Vout ±20%
4511
400
3609
3200-20
3200
Vout ±20%
5774
400
4619